Electrical Engineering
Platform
⚡ NEC 2023 · Art. 210.19

Voltage Drop Calculator — NEC 2023

Calculate voltage drop for single-phase and three-phase circuits. Verify NEC 210.19(A)(1) 3% and 5% limits instantly.

✓ Single & three-phase✓ NEC 3% / 5% compliance check✓ Wire size recommendation
EEPFree Tools › Voltage Drop Calculator

Voltage Drop Inputs

NEC 2023 Art. 210.19(A)(1) — 3% branch / 5% feeder+branch

Results

Enter values and click Calculate

Enter circuit parameters and press Calculate Voltage Drop to see results with NEC compliance check.
Wire Size Optimization & NEC Analysis🔒 Pro
Recommended wire upgrade: Increase to 10 AWG to meet 3% limit...
NEC 210.19(A)(1) FPN: Voltage drop of 3% on branch circuit and 5% combined...
Optimized wire size: Based on actual load and run length...

Voltage drop formula (NEC method)

Single-phase formula

VD = (2 × K × I × L) / CM
Where K = resistivity (12.9 Cu, 21.2 Al), I = current in amps, L = one-way length in feet, CM = circular mils of conductor.

Three-phase formula

VD = (1.732 × K × I × L) / CM
The √3 factor (1.732) accounts for the phase relationship in three-phase systems.

NEC voltage drop limits

NEC 210.19(A)(1) recommends (not mandates) a maximum of 3% voltage drop on branch circuits, and 5% total for the combined feeder and branch circuit. Many utilities and AHJs treat these as requirements.

Circular mils reference

14 AWG = 4,110 CM · 12 AWG = 6,530 CM · 10 AWG = 10,380 CM · 8 AWG = 16,510 CM · 6 AWG = 26,240 CM

Frequently asked questions

Is the NEC 3% voltage drop limit a code requirement or a recommendation?
NEC 210.19(A)(1) states the 3% limit as a Fine Print Note (FPN), which is informational — not a mandatory code requirement. However, many utilities, AHJs, and project specifications treat it as a hard requirement. For commercial and industrial projects, always verify with the local AHJ and project specifications.
What wire size should I use to limit voltage drop to 3%?
The required circular mils can be calculated as: CM = (2 × K × I × L) / (V × 0.03). For example, a 20A load at 120V running 75 feet needs approximately 6,450 CM — which is 12 AWG copper (6,530 CM). Use the Pro optimizer above to get the exact minimum wire size for any circuit.
Does voltage drop affect conductor ampacity sizing?
No — ampacity (NEC Table 310.16) and voltage drop are independent calculations. Ampacity limits the maximum current a conductor can carry safely based on heat dissipation. Voltage drop may require a larger conductor than ampacity alone dictates, especially for long runs. Always check both.

Related calculators

Get automatic wire size recommendations

Pro plan calculates the minimum wire size needed to meet NEC limits — plus exports a compliant PDF report with full codebook citations.

Start Free 14-Day Trial →