Calculate voltage drop for single-phase and three-phase circuits. Verify NEC 210.19(A)(1) 3% and 5% limits instantly.
NEC 2023 Art. 210.19(A)(1) — 3% branch / 5% feeder+branch
Enter values and click Calculate
VD = (2 × K × I × L) / CM
Where K = resistivity (12.9 Cu, 21.2 Al), I = current in amps, L = one-way length in feet, CM = circular mils of conductor.
VD = (1.732 × K × I × L) / CM
The √3 factor (1.732) accounts for the phase relationship in three-phase systems.
NEC 210.19(A)(1) recommends (not mandates) a maximum of 3% voltage drop on branch circuits, and 5% total for the combined feeder and branch circuit. Many utilities and AHJs treat these as requirements.
14 AWG = 4,110 CM · 12 AWG = 6,530 CM · 10 AWG = 10,380 CM · 8 AWG = 16,510 CM · 6 AWG = 26,240 CM
Pro plan calculates the minimum wire size needed to meet NEC limits — plus exports a compliant PDF report with full codebook citations.
Start Free 14-Day Trial →