🔌 NEC Table 310.16 · Free Tool

Cable Size Calculator

Size conductors using NEC Table 310.16 with full temperature correction (310.15(B)) and conduit fill derating (310.15(C)) applied automatically.

📐 NEC 2023 Art. 310 🌡 Temp Correction 310.15(B) 📦 Conduit Fill 310.15(C)
Conductor Parameters
Design current before any derating
Default 30°C. Attic: 40–60°C.

NEC Table 310.16 Conductor Sizing Guide

NEC Table 310.16 lists the allowable ampacity for conductors rated 0–2000V in a raceway, cable, or earth with not more than three current-carrying conductors. Before selecting a conductor size, two correction factors must be applied: temperature correction (310.15(B)) and conduit fill adjustment (310.15(C)).

For continuous loads, NEC 210.19(A) and 215.2(A) require the conductor ampacity to equal or exceed 125% of the continuous load — not just the load itself. This means the conductor must be sized for the corrected ampacity, then also checked against the 125% rule.

Frequently Asked Questions

What temperature correction factor applies in an attic?

NEC 310.15(B)(2) provides temperature correction factors. Attic spaces can reach 50–60°C in summer. For THWN-2 (90°C rated), the correction factor at 50°C is 0.82, and at 60°C is 0.71. This significantly reduces the allowable ampacity and often requires one or two sizes larger than the base table would suggest.

When does conduit fill derating apply per NEC 310.15(C)?

NEC Table 310.15(C)(1) derating applies when more than three current-carrying conductors are in a conduit: 4–6 conductors = 80%, 7–9 = 70%, 10–20 = 50%, 21–30 = 45%, 31–40 = 40%, over 40 = 35%. Neutral conductors carrying only unbalanced current do not count as current-carrying.

Can I use 75°C conductor ampacity with 90°C insulated wire?

Yes. NEC 110.14(C)(1) limits termination temperature. Most equipment is rated for 60°C or 75°C terminals, so 90°C insulated wire must be derated to the 75°C column for the final ampacity. However, the 90°C column can be used when applying correction and adjustment factors — the result must not exceed the 75°C column value for the selected size.

Does a neutral conductor count toward conduit fill?

A neutral that carries only the unbalanced load of a wye system does not count as a current-carrying conductor for conduit fill purposes (NEC 310.15(E)). However, a neutral in a 4-wire, 3-phase system serving nonlinear loads (switching power supplies, variable frequency drives) does count, as it can carry significant harmonic current.

Related Tools

Voltage Drop Calculator
NEC 210.19 — 3% / 5% limits
Breaker Sizing
NEC 210.20(A) + 240.4(D)
Transformer Sizing
NEC 450.3 OCP ratings
NEC Load Calculation
Service entrance per 220.82