Verify that an upstream overcurrent device will not trip before its downstream device clears a fault. Includes IEEE 242 (Buff Book) baseline ratios and NEC 700.32 / 701.32 / 708.54 / 517.31 selectivity requirements for emergency, legally required, and critical operations power systems.
Selective coordination is the ability of a downstream overcurrent protective device (OCPD) to open before its upstream device, isolating only the faulted circuit. This tool applies the baseline ratios from IEEE 242 — Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems (Buff Book) and flags NEC 700.32 / 701.32 / 708.54 / 517.31 jurisdictional requirements.
For these systems, the upstream OCPD must not trip for any downstream fault, up to the highest available fault current:
For these designations, IEEE 242 baseline ratios are not enough — the design must include a documented selective coordination study with manufacturer time-current curves.
Defined in NEC Article 100 as "localization of an overcurrent condition to restrict outages to the circuit or equipment affected, accomplished by the selection and installation of overcurrent protective devices and their ratings or settings". NEC 700.32 / 701.32 / 708.54 / 517.31, 700.32, 701.32, 708.54, and 517.31 mandate it on specific systems.
IEEE 242 §15.6.5 recommends a minimum 2:1 ampere ratio between upstream and downstream molded-case breakers to achieve coordination in the overload region. At currents above the upstream instantaneous pickup, the ratio is insufficient — manufacturer published tables must be consulted.
No. Series rating allows a downstream breaker to be applied at a higher interrupting rating than its individual marking, but during a fault both devices may trip. Series rating is forbidden on emergency / legally required / COPS systems by NEC 240.86(A) and the selectivity Articles.
Where two levels of NEC 230.95 ground-fault protection are required (i.e., service and feeder), they must be coordinated per NEC 230.95 informational note and 517.17 for healthcare. A typical solution is fully-adjustable LSIG settings on the upstream device with at least 100 ms time delay.